AH500 Hardware Manual
9-30
Error
code
Description Remedy
16#A0F4
The bus of AH10DNET-5A
becomes OFF.
1. Check whether the communication cable is normal, and
whether the shielded cable is grounded.
2. Check whether the serial transmission speeds of other
devices on the network are the same.
3. Check whether the both ends of the cable are connected
to 121 terminal resistors.
4. Supply power to AH10DNET-5A again.
16#A0F5
AH10DNET-5A detects that
there is no network power
supply to the DeviceNet.
Check whether the communication cable is normal, and
whether the network power supply is normal.
16#A0F6
Something is wrong with the
internal memory of
AH10DNET-5A.
Supply power to AH10DNET-5A again. If the error still
occurs, please contact the factory.
16#A0F7
Something is wrong with the
data exchange unit of
AH10DNET-5A.
Supply power to AH10DNET-5A again. If the error still
occurs, please contact the factory.
16#A0F8
The product ID of
AH10DNET-5A is incorrect.
Supply power to AH10DNET-5A again. If the error still
occurs, please contact the factory.
16#A0F9
An error occurs when the data
is read from AH10DNET-5A, or
when the data is written into
AH10DNET-5A.
Supply power to AH10DNET-5A again. If the error still
occurs, please contact the factory.
16#A0FA
The node ID of AH10DNET-5A
is the same as that of the slave
set in the scan list.
1. Set the node ID of AH10DNET-5A again. The new node
ID can not be the same as the node ID of the slave set in
the scan list. Supply power to AH10DNET-5A again.
2. Put no slave in the scan list, and download the blank
scan list to AH10DNET-5A through the simulated online
mode in the software. Supply power to AH10DNET-5A
again.
9.2.8
Troubleshooting for AH10PFBM-5A
Error
code
Description Remedy
16#A003
The master station enters the
test mode.
Just repower it.
16#A005
A timeout occurs when chips
inside the master station
communicate.
Download the appropriate configuration again. If the error
still occurs, please contact the factory.
16#A00B
A timeout occurs when
AH10PFBM-5A exchanges data
exchange with a PLC.
Repower AH10PFBM-5A . If the error still occurs, please
contact the factory.
16#A0E2
AH10PFBM-5A detects that one
slave is offline.
1. Detect if the PROFIBUS-DP bus connection is proper.
2. Detect if both ends of the network have connected the
terminal resistors respectively.
16#A0E6
The master station detects that
an error occurs in a module
connected to AHRTU-PFBS-5A.
Please check the modules connected to AHRTU-PFBS-5A.
16#A401
The configuration in the master
module is empty.
Download the appropriate configuration.
16#A402
PLC does not assign the I/O
mapping area to the master.
Assign the appropriate I/O mapping area to the master via
ISPSoft.
16#A404 Master initializing error
Contact the factory if the error still exists after repowering
AH10PFBM-5A.