Chapter 9 Troubleshooting
9-13
Error
code
Description Remedy
16#620D
The transmitted data length set in
the UDP socket function is illegal.
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module in
HWCONFIG again.
16#620E
The data which is sent through the
UDP socket exceeds the device
range.
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module in
HWCONFIG again.
16#620F
The device which receives the data
in the UDP socket function is
illegal.
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module in
HWCONFIG again.
16#6210
The received data length set in the
UDP socket function is illegal.
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module in
HWCONFIG again.
16#6211
The data which is received through
the UDP socket exceeds the
device range.
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module in
HWCONFIG again.
16#6212
There is no response from the
remote device after the timeout
period.
Make sure that the remote device is connected.
16#6213
The data received exceeds the
limit.
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module in
HWCONFIG again.
16#6214
The remote device refuses the
connection.
Make sure that the remote device operates normally.
16#6215 The socket is not opened.
Check whether operational sequence in the program is
correct.
16#6217 The socket is opened.
Check whether operational sequence in the program is
correct.
16#6218
The data has been sent through
the socket.
Check whether operational sequence in the program is
correct.
16#6219
The data has been received
through the socket.
Check whether operational sequence in the program is
correct.
16#621A The socket is closed.
Check whether operational sequence in the program is
correct.
16#6303
The remote device in the Ether
Link aborts the connection.
1. Check the connection and the status of the remote
device.
2. Check whether the remote device supports the Ether
Link.
16#6304
The connection in the Ether Link is
busy.
1. Check whether the number of connections in the
Ether Link exceeds the system load.
2. Retry the connection in the Ether Link later.
16#6309
The remote device in the Ether
Link does not respond after the
timeout period.
1. Check whether the CPU module in the Ether Link
operates normally.
2. Check whether the CPU modules are connected
normally.
16#6400
The number of TCP connections
reaches the upper limit, or the flag
which is related to the sending of
the data is not set to ON.
1. Check whether the flag which is related to the sending
of the data in the program is modified.
2. Retry the setting of the flag and the sending of the
packet.