AH500 Hardware Manual
Extension backplane
If the number of slots on the main backplane is not sufficient for the whole system, users can use the
extension backplanes to increase the number of extension modules. The extension backplanes are
divided into two types according to the number of extension modules installed on the extension backplanes.
These two types are six-slot extension backplanes, and eight-slot extension backplanes.
POWER I/O0 I/O1 I/O2 I/O3 I/O4 I/O5 I/O6 I/O7
2.1.2 Installing Modules on a Main Backplane
For a main backplane as a master, the first slot from the left is for a power supply module, the second slot is for
a CPU module, and the slots following the second slot are for extension modules. All AH500 series extension
modules can be installed on a main backplane. Eight AH500 series network modules at most can be installed
on a main backplane, but no limits are imposed on the number of other modules which can be installed on a
main backplane. No limits are imposed on the installing of modules except that a power supply module and a
CPU module have to be installed in the first slot and the second slot respectively. Therefore, users can
configure the hardware by themselves. Besides, twelve extension modules at most can be installed on a main
backplane.
For a main backplane as a RTU, the second slot is for a RTU module, and only digital input/output modules,
analog input/output modules, temperature measurement modules and AH10SCM-5A are supported.
Main backplane as a master
Main backplane as a RTU
2-8