AH500 Hardware Manual
9.1
Troubleshooting for CPU Modules
Users can get the remedies from the tables below according to the statuses of the LED indicators and the error
codes.
9.1.1
ERROR LED Indicator’s Being ON
Error
code
Description Remedy
16#000B
The program in the PLC is
damaged.
Download the program again.
16#000D The CPU parameter is damaged. Reset the CPU parameter, and download it.
16#0010
The access to the memory in the
CPU is denied.
Download the program or parameters again. If the problem
still occurs, please contact the factory.
16#0011 The PLC ID is incorrect. (SM9) Please check the PLC ID.
16#0012
The PLC password is incorrect.
(SM9)
Please check the PLC password.
16#0014
The procedure of restoring the
system can not be executed.
(SM9)
The contents of the system backup file are incorrect, or the
file does not exist in the path specified. If the file exists and
the procedure of restoring the system can not be
executed, please backing up the system again. If the error
still occurs, please contact the factory. (Please refer to
section 7.5 in AH500 Operation Manual, and section 18.2
in ISPSoft User Manual for more information about the
memory card.)
16#0015
The module table is incorrect.
(SM10)
The module table stored in the CPU module is incorrect.
Compare the module table in HWCONFIG with the actual
module configuration, and download the module table
again.
16#0016
The module setting is incorrect.
(SM10)
The module setting stored in the CPU module is incorrect.
Check whether the version of the module inserted in the
slot is the same as the version of the module in
HWCONFIG. After the version of the module is updated,
users can download the module setting again.
16#0017
The data register exceeds the
device range. (SM10)
The data register stored in the CPU module exceeds the
device range. Check whether the module parameter in
HWCONFIG is correct, and download the module
parameter again.
16#001B Timed interrupt 0 is set incorrectly.
Set the CPU parameter in HWCONFIG again, and
download the CPU parameter again.
16#001C Timed interrupt 1 is set incorrectly.
Set the CPU parameter in HWCONFIG again, and
download the CPU parameter again.
16#001D Timed interrupt 2 is set incorrectly.
Set the CPU parameter in HWCONFIG again, and
download the CPU parameter again.
16#001E Timed interrupt 3 is set incorrectly.
Set the CPU parameter in HWCONFIG again, and
download the CPU parameter again.
16#001F
The watchdog timer is set
incorrectly.
Set the CPU parameter in HWCONFIG again, and
download the CPU parameter again.
16#0020
The setting of the fixed scan time
is incorrect.
Set the CPU parameter in HWCONFIG again, and
download the CPU parameter again.
16#0021
The setting of the fixed scan time
is incorrect.
Set the CPU parameter in HWCONFIG again, and
download the CPU parameter again.
16#0022
The CPU parameter downloaded
to the PLC is incorrect.
Download the CPU parameter again.