AH500 Hardware Manual
4.2.2 Start Addresses for Analog Input/Output Modules
Input/Output data registers are automatically assigned to an analog input/output module through HWCONFIG
in ISPSoft according to the number of registers which is defined for the analog input/output module. A channel
occupies two words.
AH04AD-5A: There are 4 input channels. The input device range occupies 8 data registers.
AH08AD-5B/AH08AD-5C: There are 8 input channels. The input device range occupies 16 data registers
AH06XA-5A: There are 4 input channels, and 2 output channels. The input device range occupies 8 data
registers, and the output device range occupies 4 data registers.
AH04DA-5A: There are 4 output channels. The output device range occupies 8 data registers.
AH08DA-5B/AH08DA-5C: There are 8 output channels. The output device range occupies 16 data
registers.
4.2.3 Start Addresses for Temperature Measurement Modules
Input data registers are automatically assigned to a temperature measurement module through HWCONFIG in
ISPSoft according to the number of registers which is defined for the temperature measurement module. A
channel occupies two words.
AH04PT-5A: There are 4 input channels. The input device range occupies 8 data registers.
AH08PTG-5A: There are 8 input channels. The input device range occupies 16 data registers.
AH04TC-5A: There are 4 input channels. The input device range occupies 8 data registers.
AH08TC-5A: There are 8 input channels. The input device range occupies 16 data registers