CHAPTER 7: DIAGNOSTICS DATALOG
MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 7–9
7.7 Datalog
The Home > Diag > Datalog page displays the MM300 datalog parameters. A typical
datalog page is shown below.
Figure 8: Datalog values
# of Triggers Since Clear
Range: 0 to 65535
Count of data log triggers since the Clear Data Logger command was sent.
# of Datalog Samples Stored
Range: 0 to 256
Count of the number of samples stored in the data log for the current trigger cause.
Trigger Cause
Range: None, Command, VO1 to VO32, Any Trip Pickup, Any Trip, Any Trip Dropout, Any
Alarm Pickup, Any Alarm, Any Alarm Dropout, Any Stop, Start A, Start B
Indicates the cause of the datalog trigger.
Trigger Date
Date of the current trigger.
Trigger Time
Time of the current trigger.
Datalog Status
Range: Stopped, Started, Triggered, Pretrigger, Posttrigger
Indicates the present status of the data log feature. Stopped and Started are used only
in Continuous mode. Triggered, Pretrigger, and Posttrigger are used only in Trigger
Mode.