CHAPTER 6: SETPOINTS PROTECTION ELEMENTS
MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 6–39
NOTE
NOTE:
The ground fault protection pickup setpoints are entered in %FLA if the Ground CT setpoint
is selected as "Residual," or in units of primary amps if a 50:0.025 core balance CT is used
and the ground CT is selected as “CBCT 2000:1”.
Various situations (for example, contactor bounce) may cause transient ground currents
during motor starting that exceed the ground fault pickup levels for a very short period of
time. The delay can be fine-tuned to an application so it still responds very quickly, but
rides through normal operational disturbances. Normally, the ground fault time delays are
set as short as possible, that is, 0 ms. Time may have to be increased if nuisance tripping
occurs.
Special care must be taken when the ground input is wired to the phase CTs in a residual
connection. When a motor starts, the starting current (typically 6 × FLA for an induction
motor) has an asymmetrical or DC component. This momentary DC component will cause
each of the phase CTs to react differently, and cause a net current into the ground input of
the relay.
The following setpoints are available for the ground fault protection element.
[Path: Home > Setpoints > Protection > Electrical]
Ground Trip Level
Range: 10 to 100% FLA in steps of 1%, or OFF, when Ground CT type is set to "Residual"
Range: 0.5 to 15.0 A in steps of 0.1 A, when Ground CT type is set to "CBCT 2000:1"
Default: OFF
This setpoint specifies the ground fault trip pickup level. A value of “OFF” disables the
ground fault trip function.
Ground Trip Delay on Start
Range: 0.0 to 10.0 s in steps of 0.1 s
Default: 0.0 s
This setpoint specifies the time that the motor ground fault current must meet or exceed
pickup to generate a ground fault trip when the motor is in a starting condition.
Ground Trip Delay on Run
Range: 0.0 to 5.0 s in steps of 0.1 s
Default: 0.0 s
This setpoint specifies the time that the motor ground fault current must meet or exceed
pickup to generate a ground fault trip when the motor is in a running condition.
Ground Alarm Level
Range: 10 to 100% FLA in steps of 1%, or OFF, when Ground CT type is set to "Residual"
Range: 0.5 to 15.0 A in steps of 0.1 A, when Ground CT type is set to "CBCT 2000:1"
Default: OFF
The setpoint specifies the ground fault alarm pickup level. A value of “OFF” disables the
ground fault alarm function.
Ground Alarm Delay on Start
Range: 0 to 60 s in steps of 1 s
Default: 10 s
This setpoint specifies the time that the motor ground fault current must meet or exceed
pickup to generate a ground fault alarm.
Ground Alarm Delay on Run
Range: 0 to 60 s in steps of 1 s
Default: 10 s
This setpoint specifies the time that the motor ground fault current must meet or exceed
pickup to generate a ground fault alarm.