1–6 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
SPECIFICATIONS CHAPTER 1: INTRODUCTION
1.2 Specifications
NOTE
NOTE:
Specifications are subject to change without notice.
1.2.1 Protection specifications
ACCELERATION TIMER
Pickup:......................................................................I
av
> I
cutoff
Dropout:..................................................................I
av
< I
pu
or timer expired
Time delay: ............................................................0.5 to 250.0 seconds in steps of 0.1
Timing accuracy: ................................................±500 ms or 1.5% of total time
Elements:................................................................trip and alarm
AUXILIARY UNDERVOLTAGE
Pickup level:........................................................... 60 to 90% of NCV
Time delay: ............................................................1 to 60 seconds in steps of 1
Timing accuracy: ................................................± 500 ms
Elements:................................................................trip and alarm
CURRENT UNBALANCE
Range:......................................................................4 to 40% in steps of 1
Accuracy:................................................................±2%
Time delay: ............................................................1 to 60 seconds in steps of 1 s
Timing accuracy: ................................................±500 ms
Elements:................................................................trip and alarm
FUSE FAILURE (RUNNING STATE ONLY)
Timing:.....................................................................<500 ms
Elements:................................................................trip and alarm
GROUND FAULT (CBCT OR RESIDUAL)
Pickup level:...........................................................0.5 to 15.0 A in steps of 0.1 (CBCT); 10 to 100% of FLA in steps
of 1% (residual)
Trip time delay on start:...................................0 to 10 s in steps of 0.1 s
Trip time delay on run: .....................................0 to 5 s in steps of 0.1 s
Alarm time delay on start/run:.....................0 to 60 s in steps of 1 s
Timing accuracy: ................................................±50 ms or ±0.5% of total time
Elements:................................................................trip and alarm
LOAD INCREASE
Pickup level:........................................................... 50 to 150% of FLA in steps of 1%
Timing accuracy: ................................................±500 ms
Elements:................................................................Alarm
CALCULATION METHOD
If I
AV
I
FLA
: ( [I
M
- I
AV
] / I
AV
) x 100%
If I
AV
I
FLA
: ( [I
M
- I
AV
] / I
FLA
) x 100%
Where:
I
AV
= average phase current
I
M
= current in a phase with maximum deviation from I
AV
I
FLA
= MOTOR FULL LOAD CURRENT setpoint