CHAPTER 6: SETPOINTS PROTECTION ELEMENTS
MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 6–35
6.3.2 Mechanical protection
Select the Home > Setpoints > Protection > Mech page to edit the mechanical protection
setpoints.
Figure 27: Mechanical protection configuration setpoints
The mechanical protection setpoints are divided into the following categories.
Mechanical jam
Undercurrent protection
Underpower protection
Acceleration protection
Open control circuit trip.
The setpoints applicable to each of these categories are described in the following
sections.
6.3.2.1 Mechanical jam
After the motor has started and reached a running state, the mechanical jam element (if
enabled) produces a trip when the magnitude of Ia, Ib, or Ic reaches or exceeds the pickup
level for the time specified by the
Mechanical Jam Delay setpoint. This feature may be used
to indicate a stall condition when running. Not only does it protect the motor by taking it
off-line faster than the thermal model (overload curve), it may also prevent or limit damage
to the driven equipment if motor starting torque persists on jammed or broken equipment.
The
Mechanical Jam Level should be set higher than motor loading during normal
operation, but lower than the motor stall level. Normally the delay is set to the minimum
time delay or to avoid nuisance trips due to momentary load fluctuations.
The following setpoints are available for the mechanical jam element.
Mechanical Jam Level
Range: 1.01 to 4.50 × FLA in steps of 0.01 or OFF
Default: OFF
This setpoint specifies the current pickup level. Set this value to “OFF” to disable
mechanical jam protection.
Mechanical Jam Delay
Range: 0.1 to 30.0 seconds in steps of 0.1
Default: 0.1 seconds
This setpoint specifies the time that the motor current must reach or exceed pickup to
generate a mechanical jam trip.