81331 Rev 01 Nov 2010
19
5
Setup and Operation
Safety Precautions
F
Warning
The output of this test set can be lethal.
As with any high-voltage equipment, caution must be used at all times and all
safety procedures followed. Read and understand Section 2, Safety, before
proceeding. Be sure that the test specimen is de-energized and grounded before
making connections. Isolate power equipment to be tested from the high-voltage
busbars and attach necessary grounds to floating busbars in accordance with
standard company policy, observing all safety procedures. Make certain that no
one can come in contact with the high-voltage output terminal or any material
energized by the output. Be aware that when testing power cables high voltage
will be present at the remote end of the cable. Use protective barriers if
necessary. Locate the control unit and high-voltage unit in an area which is as dry
as possible. Maintain adequate clearances between energized conductors and
ground to prevent arc-over. Such accidental arc-over may create a safety hazard
or damage the equipment being tested.
Setup
The following steps are a general guide for setting up the test set. Figure 6 shows
a typical setup for testing inter-winding and ground capacitance on a three-phase
delta-wye power transformer; Figure 7 shows a typical setup for making
excitation current measurements on the same transformer. The test set controls
and connectors are identified in Figures 1 through 5. Refer to the Application
Guide for specific instructions on connecting this and other power equipment to
the test set.
When making capacitance measurements on transformer windings always short
each winding on itself with a jumper lead to eliminate winding inductance effect.
The shorting wire is usually non-insulated and must not be in contact with any
other insulated or non-insulated parts of the transformer.