4. Motion Control Instruction
4-120 DVP-MC operating manual
4.6.34. MOVF_R
API
Controller
161
MOVF_R
Move floating number to multiple
registers
10MC11T
Explanation of the instruction:
MOVF_R is used for sending one 32-bit floating number to multiple target registers.
When EN is on, the content of S1 is sent to the zone with D as the starting register and the data length is
specified by S2. When the data length S2 is larger than maximum 64, it is counted as 64. And the part above
64 is invalid.
Explanation of input and output parameter of the instruction:
Parameter
name
Explanation
Data
type
Available
device
EN “MOVF_R” is executed as “EN” turns on. BOOL M,I,Q, constant
S1 The source where the data comes from. REAL Constant,D
S2
The length of the transmitted zone, the max value for S2
is 64.
UINT Constant,D
D The starting one of the target registers REAL D
Note: This instruction can be used for multi-point transmission of the floating point only. For detailed
application, please refer to the example on MOVF instruction.